METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-127 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
16) Emergency fan rooms
17) Elevator equipment rooms
18) Other ancillary room doors, as needed
Card key access also shall be provided for 1) through4) above for
underground facilities only. Card key access shall be provided for 5)
above for both above and below ground facilities. Roll-up grilles will
require two card readers; one on each side of the grille.
Card key access shall also be provided for 14) to suppress alarms for
authorized entry.
Intrusion for 7), 8), 11), 12), 13) and 18) shall be recorded as an event
only for historical reporting and shall not trigger an intrusion alarm when
the area perimeter is also secured by IDS.
An intrusion concept should be developed for large facilities (like
underground stations) so that the premises are protected, but not over-
protected (too many alarms may result in the system not being utilized).
Attention should be given to protecting the perimeter – all of those doors
that are dividing the public from non-public areas. In any case, the doors
requiring card readers will remain the same.
The system shall be designed to minimize false alarms. A combination
of key bypass switches and extra card readers, or other technology
which keeps alarms from being sent when a key is used to unlock a
door, should be used so that all alarms are valid alarms, not employees
going about their daily business.
b. Yard and shop facilities and central control:
1) Communications Equipment Rooms
2) Data Processing Rooms
3) Operations Control Rooms
4) CCTV Observation Rooms
5) Operations Computer Rooms
6) Yard Control Towers
7) Train Control Rooms.
Central Control facilities
shall also have card key access.
c. Intrusion alarms shall be indicated at central control and at the EMP
d. Local audible alarms with configurable automation timed resets shall be
provided for intrusion detection at emergency exit doors and hatches
and platform end gates.
e. Passive request to exit devices shall be installed to inhibit intrusion
alarms during egress from the secure side of any monitored entrance
2. The controlled access (CA) subsystem shall include card key readers,
validating terminals and hard-copy record printers. Card readers