METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix B
DE304.09 Appendix 9B-4 Revision 1 : 05/09/12
Metro Baseline Re-Baseline: 04/20/10
Individual signal call-on for each signal
Aspect indication for each signal
Individual signal stop control for each signal. Signal stop shall cancel and established or
requested route, fleet or call-on over the signal
Time lock indication for each signal
Signal system general alarm for each controller
Interlocking routing mode indication and control
Local control panel control mode indication
Local control panel fail alarm
Signal lamp out alarm
Signal DC power fail alarm
Signal ground fault alarm
Train berthed indication for each turnback platform track
Crossing gate up and down position indication for each gate
Crossing call for each track at each crossing
Crossing lights out alarm at each crossing
Exit gate loop detector module fail alarm
Signal bungalow intrusion alarm
Signal bungalow smoke/heat detection alarm
Signal bungalow fire panel trouble alarm
TWC system trouble alarm
1.6.1.3 Train to Wayside Communications
The entire indication memory for each loop shall be block transferred to the SCADA
PLC.
Available ROC TWC controls shall be assigned to a continuous block of TWC control
memory and shall be block transferred from the SCADA PLC.
1.6.1.4 Traction Power and Auxiliary Switchgear
Breaker/Switch open and closed indication
Main and feeder AC breaker open and close control
Main and feeder DC breaker open and close control
Control mode, lockout, trip, trouble alarm for each remotely controllable device where
applicable
Utility under voltage alarm
AC and DC bus under voltage alarm
AC and DC switchgear control voltage alarm
DC feeder load voltage energized indication (>25VDC)
DC bus voltage energized indication (>25VDC)
Emergency trip active alarm
Emergency trip reset control
Emergency Trip System pushbutton pressed and depressed indication (one for each
button, including deluge)
Emergency Trip System Trouble
TPS Smoke/Heat alarm
TPS Fire panel trouble alarm