METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-98 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
Radio Antenna Sleeves consist of one and one-half inch (12") I.D. non metallic
sleeves through walls. These sleeves shall be utilized for routing of leaky coax
(radio antenna) cables, which are part of the distributed radio antenna system.
1. Sleeves shall be provided through walls, into all rooms or areas accessible
to the general public and LRT and HRT operating or maintenance personnel.
2. Sleeves shall be located as far above the finished floor as practical without
causing the antenna to interfere with any equipment on either side of the
wall.
3. Four (4) two inch (2") GRS conduits from the TC & C room to each trackway
shall be provided, total of eight (8) conduits. When the TC & C room is
located on other than the platform level, these four conduits shall extend to
the outside of the trainway.
4. Two (2) two inch (2") sleeves shall be placed vertically from the TC & C
room through the ceiling to above grade to accommodate antenna cable for
off air interfaces.
5. For those locations requiring off-air repeaters for Radio Services, required
size GRS conduit shall be provided between the TC & C Room and each
surface antenna location. Routing shall be determined on a site-by-site
basis.
G. Public Address Conduits
1. General
a. Public Address Conduits generally consist of the following:
1) Embedded conduit from the TC & C room to the speaker zone with
interruptions at speaker backboxes or junction boxes.
2) An embedded return conduit from the last speaker in a "string" to the
TC & C room.
3) Conduits in ancillary areas may be surface mount and shall have a
two-hour fire rating.
2. All conduits shall be GRS. No other circuits may be shared in a PA conduit.
All PA conduits shall originate and terminate in the TC & C room. Minimum
size is one inch (1").
3. Two separate one-inch conduits run directly from a backbox (8 x 8) or
junction box at the approximate midpoint of the mezzanine ceiling and the
midpoint of the platform ceiling to the TC & C room.
H. Closed Circuit Television Conduits
Conduits for the Closed Circuits Television system consist of two conduits in
parallel, both serving each camera location. Maximum six camera locations may